DSP-VIP-PM

Voltage-Current Based Motor Protection Relay
*Panel Flush Mounting Type:Converter,Display meter,Communication Module
*Protection:Over/Under voltage,Over/Under Load(KW)/Current,Ground fault,Over Temp,Short circuit,Shock,Locked Rotor,Phase Loss,Reverse Phase
*Indication:KW,KWH,A, V,GR,TEMP,PF(CosΘ),working time,Number of MC ON-OFF
*Additional Function:RS 422/485, Y-D,R-F,Reactor starting,Shut down delay timer & Delay on-make timer
*Pre-maintenance:Able to preset alarm point/O,U curr.GF,Temp,Shock(Stall),MOTOR working time, short circuit in Instant (within 30msec)
* Particulary Useful for process control and pre-maintenance as presetting various alarm factor

Information

Easy Handling

  • to realize convenient & various data input
    • Display Meter
    • Loader
    • Note Book PC
  • Main/Sub/Cab Menu :three seperated menu according to usage and data input frequency
    • Main menu :Data input frequency is rather higher
    • Sub menu : ratherly common application for all kind of motor
    • Cab menu(calibration menu):adjustable for indicating value within narrow range(+,- 12.7%)/this menu is appeared when “SET” key is pressed for 5 sec or more and disappeared right after pressing again
  • Back lit display:easy handling in dark space of the panel
  • To indicate a necessary in every 3 sec
    • basic factor circulating indication:V,I,KW,GR/”OFF” must be set in “rota” mode
    • Basic Factor + PF,temp,KWH,AWT(Accumulated working Time)/”ON” must be set in “rota” mode/Possible to fix one of circulated factor or to release:one touch for “CLR” key
    • Possible to check presetting value during operation / “SET” & “MODE” key / Mode and value is shown alternatively / return to operating state without input for 10 sec or pressing “Mode” key/ not possible to preset value
    • To show load factor(actual/setting)/65%~100%,Round type
  • Duplex Alarm : Higher Alarm,Lower Alarm to OC
  • To secure a safety: Password input for setting a data
  • ON-OFF switch/DSP-VIP-PM:to save wiring and labor inside panel
  • Convenient installation:65 Phi circle or rectangular hole/DSP-VIP-PM:Display Meter
  • To indicate tripped number of main contactor:contributing to check a replacing term and effective maintenance
  • To call initialized factory setting value:pressing test button before power-on and keeping a press for 3 sec after power-on.
  • To keep a stable operation under frequency variation of inverter:10 Hz~400Hz

Multi-complexed Function

  • Power type protection relay based on Voltage and Current
  • to indicate RMS value/Voltage,Current:RMS chip adopted in every input/to contribute to check an exact condition of motor
  • Provides actual meter function:V,I,KW,PF,KWH,temp
    • -Voltage Select:110V/220V/380V/440V
    • -Current Meter with CT:0.5A~3600A(Auto range for dcimal point)
    • -KW Meter:0.01~66535 KW(Auto range for dcimal point)
    • -Power factor Meter:+,-,0%~100%
    • -KWH Meter:0.1KWH~66535 KWH
    • -Temperature Meter:0 ~150 degree C
    • -Auto ramge:to indicate decimal point in conjunction with “K/Test” LED in Loader and DM
  • To cover a wide current range
    • 70 Type : 0.2 ~70A/ 0.2A~6A with an external CT(“5t” must be selected in “cto”mode)
    • With external CT:0.5A ~ 3000A
  • To realize Short,Ground fault protection by instant time:within 0.05sec
  • To be acceptable for various rating of ZCT:200/1.5mA or 200/100mV,selectable in DIP SW
  • Temperature protection/motor winding:sensed by PT100
    • Not posible to start under keeping over temperature than presetted value
    • if PT100 is not connected before starting, alarm message is coming out and not allow to start.
    • Above all condition can be clear as making temperature mode disable.
  • various and multiple output of Main and Aux internal relay
  • Main / 1a-1b(95-96,97-98) :energized with output of internal relay,C-M-D-Y,at same time
  • AUX : 1C X 1 / 07-08-10 :acts same as main trip or one of Shoc/Ec/AL/Uc/AL/Temp/Ec-tE selected in “Au-o” mode
  • 1C X1 / 27-28-30:trip for voltage protection ,but possible to change into “ALLc”(lower level alarm) in “Line” mode
  • Y-Delta Starting Timer: not neccessary for additional circuit ,to save labor and space
  • to memoize latest number of 8 tripped cause:to contribute analysing trouble cause and keeping a data after power-off
  • main contactor Auto Close:in case a line power is “ON” again within a presetting time(SDDT) after a line power is “OFF” during a normal operation,main contactor is closed automatically after another presetting time(DOMT)
  • Shut Down delay Time:1~5 sec/Adjustable
  • delay On make Time:0(Instant)~25sec/Adjustable 5 sec unit
  • Expression in mode:eg/2-3:in case power is “on” within 2 sec after power-off,motor restarts after 15 sec(3 is matched with 15 sec) from instant of power-on.
  • Self-diagonostics:main trip output is tripped after counting down o-time of definite T-I or a time of 550% to “OC” Inverse T-I

Remote Control through RS 485/422 Digital Communication

  • basically 4~20mA Output:max curremnt of 3 phase
  • To realize effective system for digital communication:posible to combine a module simply if neccessary
  • To response for RS 485/422, Modbus
  • to select one of RS485 and 422:Simply selectable in DIP SW inside communication module
  • To put easily termination resistance in extreme end unit:Simply selectable in DIP SW inside communication module
  • To monitor and input a data in the field:Note PC converter<>in DSP

Function List

Function DSP-VIPL DSP-VIPM remark
Converter +
Loader
Comm.
Module
Converter +D.
Meter
Comm.
Module
Protection Over Load/Over Current
Under Load/Under Current
Over Voltage
Under Voltage
Phase Loss by Line Voltage
Phase Loss by Load Current
Reverse phase by Line Voltage
Reverse phase by Load Current
Current Unbalance
Locked Rotor
Shock/Stall
Short Circuit Available for 10 Type
Ground fault
Over temperature
Indication Line Voltage
Load current
3 Phase Power
Power factor,KWH
Accumulated working time
Load factor/bar graph
Auxiliary Y-D Timer
2 Level Alarm
Forward-Reverse
ON-OFF SW ×
Main Contactor Auto Close
SDDR/DOMT
Communication 4~20mA × ×
RS 485/422-Modbus × ×
Interface with Note PC × ×
Specification

Technical Specification

Division Description
Line Voltage 3Phase, AC 100V~500V, 50/60㎐
Voltage setting range AC 110V Over Voltage:110V~150V, Under Voltage:70~110V
AC 220V Over Voltage:220V~290V, Under Voltage:150~220V
AC 380V Over Voltage:380~450V, Under Voltage:310~380V
AC 440V Over Voltage:440V~510V, Under Voltage:370~440V
Current setting range 03 Type 0.2~5A/120W~2.96KW(AC380V)
10 Type 0.5 ~ 15A/0.3 KW ~ 5.9KW(AC380V)
70 Type 10 ~ 70A/5.9KW ~41.4KW(AC 380V)
With external CT refer Table
Ground fault setting range Zero phase current 10mA~10A
Time setting Starting delay time(dt) OFF, 0.1~300 sec/def
over/under voltage trip delay time(ouPt) 0.1~30 sec/def
over load/over current trip delay time(ot) 0.1~60sec/def, 5~30class/Inv :refer T-I curve
under load/under current trip delay time(ut) 0.1~30sec/def
Shock/Stall trip delay time(st) within 0.05sec/instant, 0.1~3sec/def
ground fault starting delay time(Edt) OFF, 0.1~10sec/def
ground fault trip delay time(Eot) * 0.05/instant, 0.1~30sec/def
* 1~10 Class/Inv:refer T-I curve
Y-D starting transfer time(ydt) 1sec~5min/def
main contactor auto close:time/Instant or
time delay starting
– OFF : Disable
– SDDT:1~5 sec/DOMT:0(instant)-25 sec,adjustable
Allowable tolerance Voltage ±3%
Current C <= 2A : 0.1A, C > 2A : ±5%
Time t <= 2 sec : ±0.1 sec, t > 2 sec : ±5%
Power Factor ±5%
KW,kwh Cos Phi > 0.6,+,- 5%
Control power *AC 85V~AC260V,50/60Hz (DC120V~DC370V)
*DC24V
Trip output C-M-D-Y 1a(3-SPST), 3A/Resistive
Main 1a-1b(2-SPST), 3A/Resistive
Aux 1c(1-SPDT), 3A/Resistive
OV/UV 1C(1-SPDT),3A/Resistive
(Possible to transfer into 2nd alarm)
GR 1C(1-SPDT),3A/Resistive(In “Au-o” mode,AUX output
must be set “GR”
Application Environment Temperature Operating: -25℃ ~ + 70℃
Storage : -40℃ ~ + 80℃
Relative humidity 30 ~ 85%, non-condensing
Current tollerance against changeable frequency in Inverter Avg,+,-3%,10㎐ ~ 400㎐
Max Conductor Size 25sq
Insulation Resistence Circuit-case,10Mohm or more, 500VDC
High Voltage Insulation Test *Circuit-Case: AC 2000V, 60㎐, 1 min
*Contact-Contact: AC 1000V, 60㎐, 1 min
Logic Input *220VAC:150∼260VAC,50/60Hz( 220∼370VDC)/Standard*110VAC:75∼150VAC,50/60Hz( 110∼220VDC)/Optional
Screw torque Max 0.6 N.m
Frame:IEC/EN 60695-2-12 650℃
Shock:IEC/EN 60068-2-27 1/2 sine wave, 15g / 11ms
Vibration:IEC/EN 60068-2-6 5~300㎐, 4 g with Plate,1 g with rail
trip Output:IEC/EN 60947-1 690V
Dielectric Strength:IEC/EN 60947- AC 100~240V,input,output
4-1 Contact : 4㎸, Air:8㎸
Electrostatic Discharge:
IEC/EN 61000-4-2
Air : Level 3, 8㎸
Contact: Level 3, 6㎸
Radiated Electromagnetic Field
Disturbance :
IEC/EN 61000-4-3
Level 3, 10V/m
Electric Fast Transient Burst :
IEC/EN 61000-4-4
Power,relay output: Level 4, 4㎸
others : Level 3, 2㎸
Surge
:IEC/EN 61000-4-5
Relay output: 1.2×50uS, 2㎸(0。, 90。, 180。, 270。)
Digital
Communication
Physical feature 2 wire RS 485/4 wire RS 422
Address 1~255
Speed 2.4 kbps ~ 38.4 kbps
wiring connection * Input/Out : RJ 45 and/or Screw Terminal
* RJ45 and Scrw Terminal(5P) is commoned phisically
Terminal resistance * DIP S/W selection/200Ω
* Actually:220 +220→440//390 =>206 Ohm
cable Sheathed cable, 2 Pair/4 Pair
Current Loop Communication maximum value in 3 phase current
Consuming Power 10W max

Protection

Item Description remarks
Over Voltage * 110V : 110~150V
* 220V : 220 ~ 290
* 380V : 380 ~ 450
* 440V : 440 ~ 510
*The voltage over upper level of each range makes trip of over voltage
*the trip caused by voltage is resetted automatically after reaching prestting value
*Only 110V is based on a secondary voltage of PT
Under Voltage * 110V : 70~110
* 220V : 150~220
* 380V : 310~380
* 440V : 370~440
*The 3 phase voltage of lower level of each range is assumed Zero
*the trip caused by voltage is resetted automatically after reaching prestting value
Over Load
(㎾)
Trip is done if the load(KW) greater than setting value
is kept over prset O-time
Over Current Trip is done if the current greater than setting value
is kept over prset O-time
Under Load
Under Load(㎾)
Trip is done if the load(KW) smaller than setting value
is kept over preset u-time
Under Current Trip is done if the load current smaller than setting value
is kept over prset u-time
Unbalance * trip is done if the presetted current unbalance rate is kept over 8 sec
* rate=[(max. curr.- min. curr.)/max. curr.]
* 100 [100%]
Locked Rotor trip is done if 300% current greater than preset “oc”
is kept for d-time plus 0.1 sec
Shock/Stall
(instant over current)
* trip is done if a current greater than presetting value during working
is happened for presetting time
* Presetting range:180% ~ 700%
*Available for 10 type and 70 typetype,but upper limit for 70 type
is based on [(240/OC setting value)*100][%]}
,if greater than 700%, assumed 700%
Short * available for starting instant or after d-time/selectable
* Presetting range: 800% of OC~{(240/OC)*100[%]}
,maximum upper level is 2000%,
operating time is within 50ms(0.05sec)
* available for 10 Type
* short protection over 15A should be
external CT
Ground Fault trip is done if a current greater than preset zero phase current
is kept for Eot(earth operating time)
DIP SW Selection/ZCT rating:200㎃/1.5㎃
or 200㎃/100mV
Over Temperature P trip is done if temperature sensed by PT 100 greater than preset value
is kept over 8 sec
Phase Loss
by line voltage
* This protection is identified by line voltage within 0.1 sec
* “OFF” is posible in the mode
* If there is a state of phase loss in the sametime,which means normal “power off”,
this mode does not response to such state
*If phase loss is happened ,auto reset is not possible,but manual reset
Phase Loss
by load current
* This protection is identified by load current within 0.1 sec
* “OFF” is posible in the mode
* If phase loss is happened ,auto reset is not possible,but manual reset
Reverse Phase
by line voltage
* This protection is identified by line voltage within 0.5 sec
* “OFF” is posible in the mode
* If reverse phase is happened ,auto reset is not possible,but manual reset
Reverse Phase
by load current
*This protection is identified by load current within 0.5 sec
* “OFF” is possible in the mode
* If reverse phase is happened ,auto reset is not possible,but manual reset
Main contactor Auto Close *In case a line power is “on” again within presetting time(SDDT)
after a line power is “off”,main contactor is closed automatically after another presetting time(DOMT)
* SDDT:1~5 sec/DOMT:0(instant)~25sec/adjustable in 5 sec unit
eg.:if 2-3 is presetted,in case power is “on” within 2 sec after power-off,motor starts after 15 sec(3 is matched with 15 sec)