Information
Easy Handling
- to realize convenient & various data input
- Display Meter
- Loader
- Note Book PC
- Main/Sub/Cab Menu :three seperated menu according to usage and data input frequency
- Main menu :Data input frequency is rather higher
- Sub menu : ratherly common application for all kind of motor
- Cab menu(calibration menu):adjustable for indicating value within narrow range(+,- 12.7%)/this menu is appeared when “SET” key is pressed for 5 sec or more and disappeared right after pressing again
- Back lit display:easy handling in dark space of the panel
- To indicate a necessary in every 3 sec
- basic factor circulating indication:V,I,KW,GR/”OFF” must be set in “rota” mode
- Basic Factor + PF,temp,KWH,AWT(Accumulated working Time)/”ON” must be set in “rota” mode/Possible to fix one of circulated factor or to release:one touch for “CLR” key
- Possible to check presetting value during operation / “SET” & “MODE” key / Mode and value is shown alternatively / return to operating state without input for 10 sec or pressing “Mode” key/ not possible to preset value
- To show load factor(actual/setting)/65%~100%,Round type
- Duplex Alarm : Higher Alarm,Lower Alarm to OC
- To secure a safety: Password input for setting a data
- ON-OFF switch/DSP-VIP-PM:to save wiring and labor inside panel
- Convenient installation:65 Phi circle or rectangular hole/DSP-VIP-PM:Display Meter
- To indicate tripped number of main contactor:contributing to check a replacing term and effective maintenance
- To call initialized factory setting value:pressing test button before power-on and keeping a press for 3 sec after power-on.
- To keep a stable operation under frequency variation of inverter:10 Hz~400Hz
Multi-complexed Function
- Power type protection relay based on Voltage and Current
- to indicate RMS value/Voltage,Current:RMS chip adopted in every input/to contribute to check an exact condition of motor
- Provides actual meter function:V,I,KW,PF,KWH,temp
- -Voltage Select:110V/220V/380V/440V
- -Current Meter with CT:0.5A~3600A(Auto range for dcimal point)
- -KW Meter:0.01~66535 KW(Auto range for dcimal point)
- -Power factor Meter:+,-,0%~100%
- -KWH Meter:0.1KWH~66535 KWH
- -Temperature Meter:0 ~150 degree C
- -Auto ramge:to indicate decimal point in conjunction with “K/Test” LED in Loader and DM
- To cover a wide current range
- 70 Type : 0.2 ~70A/ 0.2A~6A with an external CT(“5t” must be selected in “cto”mode)
- With external CT:0.5A ~ 3000A
- To realize Short,Ground fault protection by instant time:within 0.05sec
- To be acceptable for various rating of ZCT:200/1.5mA or 200/100mV,selectable in DIP SW
- Temperature protection/motor winding:sensed by PT100
- Not posible to start under keeping over temperature than presetted value
- if PT100 is not connected before starting, alarm message is coming out and not allow to start.
- Above all condition can be clear as making temperature mode disable.
- various and multiple output of Main and Aux internal relay
- Main / 1a-1b(95-96,97-98) :energized with output of internal relay,C-M-D-Y,at same time
- AUX : 1C X 1 / 07-08-10 :acts same as main trip or one of Shoc/Ec/AL/Uc/AL/Temp/Ec-tE selected in “Au-o” mode
- 1C X1 / 27-28-30:trip for voltage protection ,but possible to change into “ALLc”(lower level alarm) in “Line” mode
- Y-Delta Starting Timer: not neccessary for additional circuit ,to save labor and space
- to memoize latest number of 8 tripped cause:to contribute analysing trouble cause and keeping a data after power-off
- main contactor Auto Close:in case a line power is “ON” again within a presetting time(SDDT) after a line power is “OFF” during a normal operation,main contactor is closed automatically after another presetting time(DOMT)
- Shut Down delay Time:1~5 sec/Adjustable
- delay On make Time:0(Instant)~25sec/Adjustable 5 sec unit
- Expression in mode:eg/2-3:in case power is “on” within 2 sec after power-off,motor restarts after 15 sec(3 is matched with 15 sec) from instant of power-on.
- Self-diagonostics:main trip output is tripped after counting down o-time of definite T-I or a time of 550% to “OC” Inverse T-I
Remote Control through RS 485/422 Digital Communication
- basically 4~20mA Output:max curremnt of 3 phase
- To realize effective system for digital communication:posible to combine a module simply if neccessary
- To response for RS 485/422, Modbus
- to select one of RS485 and 422:Simply selectable in DIP SW inside communication module
- To put easily termination resistance in extreme end unit:Simply selectable in DIP SW inside communication module
- To monitor and input a data in the field:Note PC converter<>in DSP
Function List
Function | DSP-VIPL | DSP-VIPM | remark | |||
---|---|---|---|---|---|---|
Converter + Loader |
Comm. Module |
Converter +D. Meter |
Comm. Module |
|||
Protection | Over Load/Over Current | ○ | ○ | |||
Under Load/Under Current | ○ | ○ | ||||
Over Voltage | ○ | ○ | ||||
Under Voltage | ○ | ○ | ||||
Phase Loss by Line Voltage | ○ | ○ | ||||
Phase Loss by Load Current | ○ | ○ | ||||
Reverse phase by Line Voltage | ○ | ○ | ||||
Reverse phase by Load Current | ○ | ○ | ||||
Current Unbalance | ○ | ○ | ||||
Locked Rotor | ○ | ○ | ||||
Shock/Stall | ○ | ○ | ||||
Short Circuit | ○ | ○ | Available for 10 Type | |||
Ground fault | ○ | ○ | ||||
Over temperature | ○ | ○ | ||||
Indication | Line Voltage | ○ | ○ | |||
Load current | ○ | ○ | ||||
3 Phase Power | ○ | ○ | ||||
Power factor,KWH | ○ | ○ | ||||
Accumulated working time Load factor/bar graph |
○ | ○ | ||||
Auxiliary | Y-D Timer | ○ | ○ | |||
2 Level Alarm | ○ | ○ | ||||
Forward-Reverse | ○ | ○ | ||||
ON-OFF SW | × | ○ | ||||
Main Contactor Auto Close SDDR/DOMT |
○ | ○ | ||||
Communication | 4~20mA | ○ | × | ○ | × | |
RS 485/422-Modbus | × | ○ | × | ○ | ||
Interface with Note PC | ○ | × | ○ | × |
Specification
Technical Specification
Division | Description | |
---|---|---|
Line Voltage | 3Phase, AC 100V~500V, 50/60㎐ | |
Voltage setting range | AC 110V | Over Voltage:110V~150V, Under Voltage:70~110V |
AC 220V | Over Voltage:220V~290V, Under Voltage:150~220V | |
AC 380V | Over Voltage:380~450V, Under Voltage:310~380V | |
AC 440V | Over Voltage:440V~510V, Under Voltage:370~440V | |
Current setting range | 03 Type | 0.2~5A/120W~2.96KW(AC380V) |
10 Type | 0.5 ~ 15A/0.3 KW ~ 5.9KW(AC380V) | |
70 Type | 10 ~ 70A/5.9KW ~41.4KW(AC 380V) | |
With external CT | refer Table | |
Ground fault setting range | Zero phase current | 10mA~10A |
Time setting | Starting delay time(dt) | OFF, 0.1~300 sec/def |
over/under voltage trip delay time(ouPt) | 0.1~30 sec/def | |
over load/over current trip delay time(ot) | 0.1~60sec/def, 5~30class/Inv :refer T-I curve | |
under load/under current trip delay time(ut) | 0.1~30sec/def | |
Shock/Stall trip delay time(st) | within 0.05sec/instant, 0.1~3sec/def | |
ground fault starting delay time(Edt) | OFF, 0.1~10sec/def | |
ground fault trip delay time(Eot) | * 0.05/instant, 0.1~30sec/def * 1~10 Class/Inv:refer T-I curve |
|
Y-D starting transfer time(ydt) | 1sec~5min/def | |
main contactor auto close:time/Instant or time delay starting |
– OFF : Disable – SDDT:1~5 sec/DOMT:0(instant)-25 sec,adjustable |
|
Allowable tolerance | Voltage | ±3% |
Current | C <= 2A : 0.1A, C > 2A : ±5% | |
Time | t <= 2 sec : ±0.1 sec, t > 2 sec : ±5% | |
Power Factor | ±5% | |
KW,kwh | Cos Phi > 0.6,+,- 5% | |
Control power | *AC 85V~AC260V,50/60Hz (DC120V~DC370V) *DC24V |
|
Trip output | C-M-D-Y | 1a(3-SPST), 3A/Resistive |
Main | 1a-1b(2-SPST), 3A/Resistive | |
Aux | 1c(1-SPDT), 3A/Resistive | |
OV/UV | 1C(1-SPDT),3A/Resistive (Possible to transfer into 2nd alarm) |
|
GR | 1C(1-SPDT),3A/Resistive(In “Au-o” mode,AUX output must be set “GR” |
|
Application Environment | Temperature | Operating: -25℃ ~ + 70℃ |
Storage : -40℃ ~ + 80℃ | ||
Relative humidity | 30 ~ 85%, non-condensing | |
Current tollerance against changeable frequency in Inverter | Avg,+,-3%,10㎐ ~ 400㎐ | |
Max Conductor Size | 25sq | |
Insulation Resistence | Circuit-case,10Mohm or more, 500VDC | |
High Voltage Insulation Test | *Circuit-Case: AC 2000V, 60㎐, 1 min *Contact-Contact: AC 1000V, 60㎐, 1 min |
|
Logic Input | *220VAC:150∼260VAC,50/60Hz( 220∼370VDC)/Standard*110VAC:75∼150VAC,50/60Hz( 110∼220VDC)/Optional | |
Screw torque | Max 0.6 N.m | |
Frame:IEC/EN 60695-2-12 | 650℃ | |
Shock:IEC/EN 60068-2-27 | 1/2 sine wave, 15g / 11ms | |
Vibration:IEC/EN 60068-2-6 | 5~300㎐, 4 g with Plate,1 g with rail | |
trip Output:IEC/EN 60947-1 | 690V | |
Dielectric Strength:IEC/EN 60947- | AC 100~240V,input,output | |
4-1 | Contact : 4㎸, Air:8㎸ | |
Electrostatic Discharge: IEC/EN 61000-4-2 |
Air : Level 3, 8㎸ Contact: Level 3, 6㎸ |
|
Radiated Electromagnetic Field Disturbance : IEC/EN 61000-4-3 |
Level 3, 10V/m | |
Electric Fast Transient Burst : IEC/EN 61000-4-4 |
Power,relay output: Level 4, 4㎸ others : Level 3, 2㎸ |
|
Surge :IEC/EN 61000-4-5 |
Relay output: 1.2×50uS, 2㎸(0。, 90。, 180。, 270。) | |
Digital Communication |
Physical feature | 2 wire RS 485/4 wire RS 422 |
Address | 1~255 | |
Speed | 2.4 kbps ~ 38.4 kbps | |
wiring connection | * Input/Out : RJ 45 and/or Screw Terminal * RJ45 and Scrw Terminal(5P) is commoned phisically |
|
Terminal resistance | * DIP S/W selection/200Ω * Actually:220 +220→440//390 =>206 Ohm |
|
cable | Sheathed cable, 2 Pair/4 Pair | |
Current Loop Communication | maximum value in 3 phase current | |
Consuming Power | 10W max |
Protection
Item | Description | remarks |
---|---|---|
Over Voltage | * 110V : 110~150V * 220V : 220 ~ 290 * 380V : 380 ~ 450 * 440V : 440 ~ 510 |
*The voltage over upper level of each range makes trip of over voltage *the trip caused by voltage is resetted automatically after reaching prestting value *Only 110V is based on a secondary voltage of PT |
Under Voltage | * 110V : 70~110 * 220V : 150~220 * 380V : 310~380 * 440V : 370~440 |
*The 3 phase voltage of lower level of each range is assumed Zero *the trip caused by voltage is resetted automatically after reaching prestting value |
Over Load (㎾) |
Trip is done if the load(KW) greater than setting value is kept over prset O-time |
|
Over Current | Trip is done if the current greater than setting value is kept over prset O-time |
|
Under Load Under Load(㎾) |
Trip is done if the load(KW) smaller than setting value is kept over preset u-time |
|
Under Current | Trip is done if the load current smaller than setting value is kept over prset u-time |
|
Unbalance | * trip is done if the presetted current unbalance rate is kept over 8 sec * rate=[(max. curr.- min. curr.)/max. curr.] * 100 [100%] |
|
Locked Rotor | trip is done if 300% current greater than preset “oc” is kept for d-time plus 0.1 sec |
|
Shock/Stall (instant over current) |
* trip is done if a current greater than presetting value during working is happened for presetting time * Presetting range:180% ~ 700% *Available for 10 type and 70 typetype,but upper limit for 70 type is based on [(240/OC setting value)*100][%]} ,if greater than 700%, assumed 700% |
|
Short | * available for starting instant or after d-time/selectable * Presetting range: 800% of OC~{(240/OC)*100[%]} ,maximum upper level is 2000%, operating time is within 50ms(0.05sec) |
* available for 10 Type * short protection over 15A should be external CT |
Ground Fault | trip is done if a current greater than preset zero phase current is kept for Eot(earth operating time) |
DIP SW Selection/ZCT rating:200㎃/1.5㎃ or 200㎃/100mV |
Over Temperature | P trip is done if temperature sensed by PT 100 greater than preset value is kept over 8 sec |
|
Phase Loss by line voltage |
* This protection is identified by line voltage within 0.1 sec * “OFF” is posible in the mode |
* If there is a state of phase loss in the sametime,which means normal “power off”, this mode does not response to such state *If phase loss is happened ,auto reset is not possible,but manual reset |
Phase Loss by load current |
* This protection is identified by load current within 0.1 sec * “OFF” is posible in the mode |
* If phase loss is happened ,auto reset is not possible,but manual reset |
Reverse Phase by line voltage |
* This protection is identified by line voltage within 0.5 sec * “OFF” is posible in the mode |
* If reverse phase is happened ,auto reset is not possible,but manual reset |
Reverse Phase by load current |
*This protection is identified by load current within 0.5 sec * “OFF” is possible in the mode |
* If reverse phase is happened ,auto reset is not possible,but manual reset |
Main contactor Auto Close | *In case a line power is “on” again within presetting time(SDDT) after a line power is “off”,main contactor is closed automatically after another presetting time(DOMT) * SDDT:1~5 sec/DOMT:0(instant)~25sec/adjustable in 5 sec unit |
eg.:if 2-3 is presetted,in case power is “on” within 2 sec after power-off,motor starts after 15 sec(3 is matched with 15 sec) |
DWG
Note
Note